Caminho de cabos em chapa EKS perfurado 60x500x3000 Aço galvanizado por imersão a quente após maquinação
Cable Routes
Caminho de cabos em chapa EKS perfurado 60x500x3000 Aço galvanizado por imersão a quente após maquinação
Manufacturer Ref:
6056989
Nortécnica Ref:
EAN:
4012196333554
Description
Technical Information
Attributes
Colour
-
Width
500
Model
Without connector
Height
60
RAL-number
-
Surface protection
Hot-dip galvanised
EF000141
EV000115
Weight
9.02
Material thickness
2
Side perforation
Yes
Material quality
-
Length
3000
Operating temperature
-
-
Material
Steel
Bottom perforation
Yes
Usable cross section
29800
NATO-mounting holes
No
Working length
-
Suitable for circuit integrity
No
With cover
No
Load test type according to IEC 61537
Type II
Possible support spacing
1.5
3
Safe working load according to IEC 61537 with support spacing 0.5 m
-
Safe working load according to IEC 61537 with support spacing 1.0 m
-
Safe working load according to IEC 61537 with support spacing 1.5 m
2100
Safe working load according to IEC 61537 with support spacing 2.0 m
1350
Safe working load according to IEC 61537 with support spacing 2.5 m
1150
Safe working load according to IEC 61537 with support spacing 3.0 m
900
Safe working load according to IEC 61537 with support spacing 4.0 m
-
Safe working load according to IEC 61537 with support spacing 5.0 m
-
Safe working load according to IEC 61537 with support spacing 6.0 m
-
Safe working load according to IEC 61537 with support spacing 7.0 m
-
Safe working load according to IEC 61537 with support spacing 8.0 m
-
Safe working load according to IEC 61537 with support spacing 10.0 m
-
Safe working load according to IEC 61537 with support spacing 9.0 m
-
Safe working load according to IEC 61537 with support spacing 11.0 m
-
Safe working load according to IEC 61537 with support spacing 12.0 m
-
Brands
80686
Technical Sheet