MS116-16 Manual Motor Starter 10 ... 16 A
ABB

Cutting and Protection Devices

MS116-16 Manual Motor Starter 10 ... 16 A

Nortécnica Ref: 27DMS116-16
EAN: 4013614320347

Description

The MS116-16 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 45 mm width device with a rated operational current of Ie = 16.0 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 16 kA at 400 VAC and trip class 10A. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and single-phase applications. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks and locking devices for protection against unauthorized changes are available as accessory.

Technical Information

Attributes
Width
45
Height
90
Depth
85.6
Rated operation power at AC-3, 400 V
7.5
With integrated auxiliary switch
No
Corrente permanente nominal Iu
16
With integrated under voltage release
No
Number of poles
3
Rated operating voltage
690
690
Overload release current setting
10
16
Power loss
8.4
Degree of protection IP
IP20
With thermal overload protection
Yes
Type of electrical connection of main circuit
Screw connection
Type of control element
Turn button
Switch off technique
Thermomagnetic
Rated operation power at AC-3, 230 V
7.5
Rated short-circuit breaking capacity Icu at 400 V, AC
16
Adjustment range undelayed short-circuit release
240
240
Phase failure sensitive
Yes
Device construction
Complete device in housing
Brands
ABB
Descrição Longa
The MS116-16 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 45 mm width device with a rated operational current of Ie = 16.0 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 16 kA at 400 VAC and trip class 10A. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and single-phase applications. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks and locking devices for protection against unauthorized changes are available as accessory.

Technical Sheet